Reliability Evaluation of Hydro-Electric Power Stations in Nigeria. (A case Study of Kainji Units 1G7 & IG8 and Shiroro Units 411G1 & 411G2)
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Journal of Asian Scientific Research http://www.aessweb.com/archives.php?m=October2011&id=5003
DOI
Abstract
This research paper aims at evaluating the reliability performance of two units each
from Shiroro and Kainji hydro electric power stations of Nigeria. The result of this
study is intends to provide the basis for planning generation expansion of hydro
electric power stations in Nigeria. Herein reliability evaluation based on the Frequency
and Duration (F & D) approach is adopted. A set of reliability parameters which
quantify generating unit reliability, are computed for each unit using the annual outage
durations for the period of the study (2005-2009). The system failure probability
(unavailability), frequency of system failure (FF), and the mean duration of system
failure (TF) for each unit were obtained and fully discussed. The reliability of the
individual unit was also computed for the period of study. The study generally shows
that the generating units at Kainji Hydro Power Stations have not been adequately
maintained, leading to frequent and delayed forced outage. This indicates unreliable
performance of the individual units and the entire stations as compared with Shiroro
Hydro Power Station.
Description
Keywords
Citation
Olatomiwa L. J and Nwohu M.N. (2011). Reliability Evaluation of Hydro-Electric Power Stations in Nigeria. (A case Study of Kainji Units 1G7 & IG8 and Shiroro Units 411G1 & 411G2). Journal of Asian Scientific Research, Vol.1, No.6, ISSN 2223 1331, pp. 320 – 327