Abstract
Pharmaceutical factory workers spend 37.5% of their daily time in the production hall
manufacturing drugs used for human health needs. There is usually little or no time given to
spend in the natural environment. This affects their sanity and well-being. The Pharmaceutical
factory building (PFB) is classified as a specialised, controlled, or restrictive building; it provides
little or no access to natural environmental conditions like ventilation and lighting, thereby
increasing the financial implication of energy for the operation of drug production. Hence,
the survey was conducted to identify the factors that influence indoor environmental
performance (IEP) of PFBs. The factors responsible for influencing the indoor air quality were
measured through a survey conducted in Lagos and Ogun States, Nigeria, on 14 PFBs to
determine the value of these factors identified, using principal component analysis (PCA),
Bartlett Test, and Kaiser-Mayer Olkin (KMO): the conditions for PCA were also observed. PCA
is a factors or data reduction technique to select a subset of highly predictive factors from the
larger group of factors identified from the study. Indoor environmental quality variables are satisfied
the condition for PCA, while thermal performance variables did not meet the condition. PCA
was conducted for Indoor environmental quality and the result showed 2 major factors explaining
the variation in the original set of variables. Whereby CO2, P.M.1.0, P.M.2.5, P.M.10, HCHO,
airflow, AQICN, and AQIUS as component 1 and 2, and TVOC as component 2, the data set was also
compared with the standards recommended for indoor environmental quality and thermal
performance variables. It was found that at an average air velocity of 29oC and RH of 60%, the
average CO, TVOC, PM2.5, and PM10 were 0.25ppm, 0.31ppm, 33.92ppm, and 43.48ppm
respectively for the PFBs. Because thermal performance includes several dependent variables,
greater research on the indoor environment of PFBs in Nigeria is recommended to determine the
impact of indoor environmental characteristics on thermal parameters.