dc.identifier.citationOlatomiwa L. J and Nwohu M.N. (2011). Reliability Evaluation of Hydro-Electric Power Stations in Nigeria. (A case Study of Kainji Units 1G7 & IG8 and Shiroro Units 411G1 & 411G2). Journal of Asian Scientific Research, Vol.1, No.6, ISSN 2223 1331, pp. 320 – 327en_US
dc.identifier.issn2223 1331-
dc.identifier.urihttp://repository.futminna.edu.ng:8080/jspui/handle/123456789/9327-
dc.description.abstractThis research paper aims at evaluating the reliability performance of two units each from Shiroro and Kainji hydro electric power stations of Nigeria. The result of this study is intends to provide the basis for planning generation expansion of hydro electric power stations in Nigeria. Herein reliability evaluation based on the Frequency and Duration (F & D) approach is adopted. A set of reliability parameters which quantify generating unit reliability, are computed for each unit using the annual outage durations for the period of the study (2005-2009). The system failure probability (unavailability), frequency of system failure (FF), and the mean duration of system failure (TF) for each unit were obtained and fully discussed. The reliability of the individual unit was also computed for the period of study. The study generally shows that the generating units at Kainji Hydro Power Stations have not been adequately maintained, leading to frequent and delayed forced outage. This indicates unreliable performance of the individual units and the entire stations as compared with Shiroro Hydro Power Station.en_US
dc.language.isoenen_US
dc.publisherJournal of Asian Scientific Research http://www.aessweb.com/archives.php?m=October2011&id=5003en_US
dc.relation.ispartofseriesVol 1(6);-
dc.subjectReliability Indices,en_US
dc.subjectAvailabilityen_US
dc.subjectOutage probabilityen_US
dc.subjectReliabilityen_US
dc.titleReliability Evaluation of Hydro-Electric Power Stations in Nigeria. (A case Study of Kainji Units 1G7 & IG8 and Shiroro Units 411G1 & 411G2)en_US