Please use this identifier to cite or link to this item: http://repository.futminna.edu.ng:8080/jspui/handle/123456789/8587
Full metadata record
DC FieldValueLanguage
dc.contributor.authorAmbafi, J. G.-
dc.contributor.authorAdamu, S. S.-
dc.date.accessioned2021-07-11T20:01:42Z-
dc.date.available2021-07-11T20:01:42Z-
dc.date.issued2019-11-
dc.identifier.citationAMBAFI, J. G. and ADAMU S. S. (2019). Optimal siting, sizing, and parameters tuning of STATCOM, SSSC using MPSO and remote coordination of the FACTS for oscillation damping of power systems. Turkish Journal of Electrical Engineering & Computer Science. doi: 10.3906/elk-1811-14en_US
dc.identifier.otherdoi:10.3906/elk-1811-14-
dc.identifier.urihttp://repository.futminna.edu.ng:8080/jspui/handle/123456789/8587-
dc.descriptionRole of FACTS devices in oscillation damping.en_US
dc.description.abstractIn electromechanical oscillation damping within power system, power system stabilizers (PSSs) are often deployed. However, a PSS is less effective in damping interarea oscillation and is limited by changes in network confguration due to weak tie-lines and load variations. Consequently, this paper presents a wide-area coordination approach that damps interarea oscillations using FACTS devices and phasor measurement units. We selected a static synchronous compensator (STATCOM) and static series synchronous compensator (SSSC) for realistic power system interarea oscillation damping. The performance of the coordinated FACTS installed in a power system depends on their suitable locations, sizes, tuned parameters, and remote input signal selection. Hence, we formulated a multiobjective problem to provide the STATCOM and SSSC’s optimal solutions using multiobjective particle swarm optimization. In addition, we employed a participation factor to select suitable generator speed deviations as the wide area stabilizing signal. The proposed approach was tested on different confgurations of the Kundur 2-area 4-machine test system within MATLAB and Psat environments. The outcome of the nonlinear simulation proved that the multimachine power system stability was enhanced.en_US
dc.description.sponsorshipTETFUNDen_US
dc.language.isoenen_US
dc.publisherTubitaken_US
dc.relation.ispartofseries27;-
dc.subjectFACTS devices, interarea oscillations, phasor measurement units,en_US
dc.subjectstability, wide-area, coordinationen_US
dc.titleOptimal siting, sizing, and parameter tuning of STATCOM and SSSC using MPSO and remote coordination of the FACTS for oscillation damping of power systemsen_US
dc.typeArticleen_US
Appears in Collections:Electrical/Electronic Engineering

Files in This Item:
File Description SizeFormat 
elk-27-6-40-1811-14.pdfRole of FACTS devices in oscillation damping.509.61 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.