Please use this identifier to cite or link to this item: http://repository.futminna.edu.ng:8080/jspui/handle/123456789/10191
Full metadata record
DC FieldValueLanguage
dc.contributor.authorNwohu, Mark-
dc.contributor.authorTanko, Bashir-
dc.contributor.authorOhize, Henry-
dc.contributor.authorSadiq, Ahmed-
dc.contributor.authorUsman, Abraham-
dc.date.accessioned2021-07-17T12:48:11Z-
dc.date.available2021-07-17T12:48:11Z-
dc.date.issued2017-10-01-
dc.identifier.citationM.N Nwohu, B. Tanko, Ohize, H.O, A.A Sadiq and A. A. Usman. “Harmonic Load Modelling: A Case Study of 33KV Abuja Steel Mill Feeder” Nigeria Journal of Technology. Volume 36 No. 4, Page 1184-1190 October 2017.en_US
dc.identifier.issn0331-8443-
dc.identifier.urihttp://repository.futminna.edu.ng:8080/jspui/handle/123456789/10191-
dc.description.abstractAn in-depth study of the harmonic orders inherent in a power system network is required before mitigation techniques are adopted. This paper studied the harmonic orders of the 33 kV Abuja Steel Feeder modeled as a harmonic source using measured data. Readings of kW, kVar, kV and Hz were obtained using power quality analyzer (PQube) to identify the trend and the harmonic unbalance on the feeder. Electrical Transient Analyzer Program (ETAP) software package was deployed to perform Discrete Fast Transform (DFT) while the input parameters were the resultant relative amplitudes and phase angles for both the current and voltage source models. The current source model spectrum of the feeder under study revealed that the 11 and 13 harmonic orders have the highest percentage of amplitude relative to the fundamental compared to the other harmonics. On the other hand, the voltage source model spectrum showed that the 14th, 15th, 16th, 17th , 32nd, 33rd, and 34 harmonic orders have higher percentage of relative amplitude. However, only the 3 and 5th harmonic orders were found to cause severe harmonic distortion of voltage and current after harmonic analysis and frequency scan were performed on the ETAP platform.en_US
dc.description.sponsorshipSelfen_US
dc.language.isoenen_US
dc.publisherNigerian Journal of Technology (NIJOTECH)en_US
dc.subject: Harmonic order; Power quality; Transmission grid; ETAP; Tuned filtersen_US
dc.titleHarmonic Load Modelling: A Case Study of 33KV Abuja Steel Mill Feederen_US
dc.typeArticleen_US
Appears in Collections:Electrical/Electronic Engineering

Files in This Item:
File Description SizeFormat 
Harmonic_load_modeling_a_case_study_of_33_kV_Abuja.pdf786.12 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.